1.1 Fuel tank level: The fuel tank level should not be lower than 75% of the tank level or the FM diesel fire pump control cabinet sends a low fuel level alarm. If there is any shortage, it should be replenished in a timely manner.
1.2 Lubricating oil level: Observe the marking on the lubricating oil scale. If it is insufficient, fill it to the specified amount (in the middle of the marking), but do not exceed the upper limit of the scale marking.
1.3 Battery cable connector: Check whether there is any looseness during manual pulling. If any looseness is found, tighten it in a timely manner.
1.4 Cooling level: Observe whether the cooling liquid in the water tank is sufficient (not less than 80% of the tank level), and immediately replenish it if insufficient.
1.5 Air intake filter: Observe whether there is any foreign matter attached to the intake port of the air intake filter, and immediately clean it if found.
1.6 Start and operate the diesel fire pump for 30 minutes according to FM regulations. During operation, such data as the number of revolutions, lubricating oil pressure, battery voltage, water temperature, cooling water pressure, and pump outlet pressure should be recorded;